Digital Mains Frequency Indicator Model: MFM - 4
|
Digital Mains Frequency Trip Unit Model: MFC - 44
| Frequency
Instruments
* Range 45.00 to 99.99 Hz with ±
0.01 Hz Accuracy |
|
| SALIENT FEATURES |
* Indicator with Upper and Lower Trip Limits * Digital Display |
| SPECIFICATIONS 1. Range |
45.00 Hz to 99.99 Hz |
| 2. Resolution | 0.01 Hz |
| 3. Time-Base | Quartz-crystal |
| 4. Accuracy | ± 0.01 Hz |
| 5. Display | 4 Digit, 0.5" ht., red LED |
| 6. Display Up-date Rate | 1 Second |
| 7. No. of Limits | 2 |
| 8. Output | NO / NC relay contacts rates at 6A / 230 VAC (resistive) for each limit |
| 9. Output Logic | High & Low frequency tripping |
| 10.Mode of setting | By 4 digit Thumbwheel switches on front panel for each limit |
| 11. Supply Voltage | 230 VAC ± 10% |
| 12. Dimensions (in mm) | 96(H) X 96(W) X 150(D) |
| 13. Mounting (panel cut-out in mm) | 92 X 92 |
| 14. Options | Other voltages like 12 / 24/ 110 / 440 / 1100 VAC |